PIR Passive infrared
Motion sensor with ON/OFF delay. For ceiling installation, 360° coverage area.
Calectro’s motion sensors are primarily intended for use within ventilation and lighting control.
By detecting activity in rooms, it is possible to control the ventilation and lighting only when actually required, thus saving energy.
PIR-TF-25-360 motion sensor is a very reliable double-element detector. The sensor is housed in an elegant white cover. The lens has 360° detection coverage to ensure motion detection in a reliable way. The ON-and OFF-delays can be selected by means of jumpers.
Sensor placement:
Locate the sensor so that the probable direction of movement of a person will be across the detection zones. It is easiest for the PIR-TFT sensor to distinguish movement in this direction. Avoid possible sources of fault alarms, such as: direct sunlight, strong sources of heat (radiators, copiers, etc.), moving objects such as fans or pet animals, within the sensor’s field of view. Avoid objects that may block the detection area, e.g. large pieces of furniture, curtains, etc.
Installation:
1. Open the front cover by loosing the locking screw. Remove the circuit board from the case bottom.
2. Select wall, corner or ceiling installation. Then punch out suitable “knock outs” for the screws and fit the case bottom.
3. Replace the circuit board and connect the wires.
4. Remember to seal all unused cable entries and screw holes to stop false alarms caused by insects, etc.
5. Replace the front cover; the walk test can then proceed.
6. NB: Before changing the delay settings, switch off the detector supply voltage.
Walk test:
First ensure that the delay jumper connectors are in the “A” position (shortest delay). Turn on the power supply and wait for about 45 seconds for the sensor to warm up. Now perform the walk test by walking slowly through the entire detection area; pass through all detection zones while keeping an eye on the walk test LED. The LED should light every time you change zones. Let the unit stabilize for about 2 seconds between each test.